Tested application and requirement
Applied for 750KV and under 750KV GIS AC withstand voltage test, test frequency 30-300Hz,test voltage not more than 1000kV, test time 1min.
Work condition
environment temperature:-100C –50 0C;
2. relative humidity:≤90%RH
3. altitude: ≤1000m
Main technical parameters and functions
rated capacity:5000kVA;
input power: 3 phase 380V, 50Hz;
rated voltage:1000kV;
rated current: 5A;
working frequency:30-300Hz;
output waveform:sine wave
waveform deviation factor:Distortion rate of output voltage waveform≤1%;
working time:under rated load allowed continuous working 60min;over voltage 1.1 times 1min;;
Temperature rise:under rated load allowed continuous working 60min, after that temperature rise≤65K
quality factor: Q≥30(f=45Hz)
defensive function: Over-current, over-voltage and flashover protection are provided for the tested product (see frequency conversion power supply for details).
accuracy:System effective value 1.5;
Test standard
GB10229-88 《reactor》
GB1094 《power transformer》
GB50150-2016 《the standard for electrical equipment handover and commission test》
DL/T 596-2021 《 preventive testing rule of electrical equipment》
GB1094.1-GB1094.6-96 《Shell protection grade》
GB2900 《electrotechnical terminology》
GB/T16927.1~2-1997 《High voltage test technique》
Capacity determination
Test system total capacity is 5000kVA/1000kV, design 4 reactors, and 1250kVA/250kV/5A/140H for single reactor.
Verification: Using four reactors in series (coefficient 1.2), then L=140*4*1.2=672H
Test frequency:f=1/2π√LC=1/(2×3.14×√672×0.015×10-6)=50.13Hz
Test current:I=2πfCUtest =2π×50.13×0.015×10-6×1000×103=4.72A
Test combination
|
Combination Test object |
Reactor 1250kVA/250kV*4 |
Excitation transformer output selection |
Test voltage (kV) |
|
750KV GIS |
Use 4 reactors in series |
40kV |
≤1000kV |
System and parameters
exciting transformer JLB-200kVA/20/40kV/0.4kV 1set
rated capacitance:200kVA;
input voltage:0-400V,single phase;
output voltage:20/40kV
Structure:oil type;
weight:1T;variable frequency power supply CHXB-200kW/380V 1 set
Rated output capacity:200kW
Power supply for working: 380±10%V(single/3phase),power frequency
output voltage:0 –400V,single,
Rated input current:500A
rated output current:500A
Voltage resolution: 0.01kV
Accuracy of voltage measurement:1.5%
Frequency range:30 – 300Hz
Frequency control resolution:≤0.1Hz
requency stability: 0.1%
Running time:Continuous at rated capacity 5min
Continuous at rated capacity 5minmax temperature of components≤65K
The noise level:≤50dB
The following functions can be implemented
Variable frequency power supply is placed vertically and horizontally, especially suitable for field operation and observation.
Inside and outside are equipped with special shock-absorbing rubber support feet and protective aluminum box, which can effectively reduce bump vibration during transportation and shock during lifting. Guaranteed long-term stability and reliability of variable frequency power supply;
parameter display:Touch or external mouse large screen LCD display system. Display resonant voltage (the target voltage set before the test), Test frequency, measurement frequency, low-voltage voltage, low-voltage current, withstand voltage time, overvoltage protection, overcurrent protection, flashover protection, step boosting and timing, operation mode switching, Capacitance, inductance, frequency interchange calculation, parameter query, can also display frequency curve, voltage curve and so on to directly judge the resonance frequency accuracy and stability of the test.
parameter setting:Large screen touch LCD color screen and external mouse directly complete the setting of various parameters, can set start frequency, stop frequency, start voltage, phase boost and timing, measurement of voltage divider variation ratio, excitation variation ratio, overvoltage protection, overcurrent protection, flashover protection, test mode, capacitance and inductance frequency interchange calculation, parameter setting tips and help, etc.
Test mode:Touch screen and external mouse operation,there are three running states: automatic, semi-automatic and manual. Have the features of boosting, tuning (including manual and automatic), segmenting pressurization and timing, running state, mode switching, fault warning, frequency interchange calculation of capacitance and inductance, etc.
Protection function and information prompt: with high pressure overvoltage protection, low pressure overcurrent protection, overcurrent protection, and detuning protection, zero, flashover protection, emergency shutdown, under voltage protection and other multiple protection functions
Data storage function:Test results saving (manual saving), printing, uploading, check back, etc
test result:After the manual or automatic test, the detailed parameters of the test can be displayed in the test result interface. When the test is interrupted, the interrupt status can be prompted. The parameters can be saved in a memory, which is a non-volatile memory and can hold 50 test records.;
Data review:The saved test result data can be displayed on the screen. It also has a USB interface, which can print the data output or use the printer carried by the device(The printer is the customer's own choice. If the customer has this requirement, it shall be specified in the contract)
Automatic voltage stabilizing function: The system automatically tracks and maintains the stable test voltage according to the set test voltage or the result of manual boost,Voltage stability can be reached to 1.0%;
The frequency range and frequency resolution can be set:The frequency modulation range can be set as 20 ~300Hz, 45 ~100Hz,200-300Hz, according to the need to set,can speed up the tuning process;Frequency resolution can set as required such as 0.1Hz,0.2Hz,0.5Hz, or1.0Hz, optimize the balance between tuning efficiency and tuning accuracy;
Frequency regulation is divided into rough and fine tuning,test resonance point can be found automatically,ensure that the resonant frequency does not drift during the whole test process;
Weight:About 85kg
HV reactor DK-1250kVA/250kV 4nos
Rated capacitance:1250kVA;
Rated voltage:250kV;
Rated current:5A;
inductance:140H /nos
quality factor:Q≥30 (f=45Hz);
Structure:oil type;
weight:about 1.2T;
capacitive voltage divider FRC-1000kV/500pF 1 set
Rated voltage:1000kV;
HV capacitance:500pF;
dielectric loss:tgσ≤0.5%;
ratio of voltage divider:10000:1
measurement accuracy:active value 1.5
weight:about 150kg;
Packing list
configuration equipment list
|
no |
name |
Model and specification |
unit |
Qty |
remarlk |
|
1 |
Exciting transformer |
JLB-200kVA/20/40kV/0.4kV |
set |
1 |
|
|
2 |
variable-frequency power supply |
CHXB-200kW/380V |
set |
1 |
|
|
3 |
High voltage reactor |
DK-1250kVA/250kV |
set |
4 |
|
|
4 |
capacitive voltage divider |
FRC-1000kV/500pF |
set |
1 |
|
|
6 |
Internal connection wires |
set |
1 |
Documents list
|
No |
name |
unit |
qty |
remark |
|
1 |
Ex-Factory test report |
copy |
1 |
|
|
2 |
manual |
copy |
1 |
|
|
3 |
Product certificates and customer comment CARDS |
set |
1 |
After-sales service
After received, according to the terms of contract about related commissioning of equipment, if necessary, the supplier shall be responsible for the on-site technical support services of relevant technicians of the equipment. Guide and assist the buyer to complete the first site acceptance test of the equipment and the technical training of relevant operation personnel of the buyer. After the acceptance, the buyer shall fill in the equipment acceptance/maintenance report (see the attached table) provided by the supplier as evidence of the completion of the acceptance.
The supplier shall carry out warranty for the set of equipment, and the warranty period shall be one year from the date of delivery. During the warranty period, the supplier shall be responsible for the free inspection and replacement of parts and components of the product (the main part of the equipment, excluding consumable accessories such as wiring)
If the warranty period exceeds one year, the product supplier will provide lifetime maintenance. If the warranty period is longer than one year, the supplier will pay the normal maintenance fee (maintenance hour fee, material fee, and additional fee).
Implement all-weather technical response service, provide technical solution within 8 hours after receiving the phone or fax about the problems in the use of this set of products.
If the equipment is damaged or unusable due to improper operation or force majeure, it is not covered by this warranty.