Three documents act together, and confusing them is the most common source of arguments on site. IEC 62271-203 is the product standard for gas-insulated metal-enclosed switchgear above 52 kV and defines the dielectric, tightness and partial-discharge performance the design must achieve. IEC 62271-1 supplies the common specifications and the test procedures used to prove it. IEC 60480 covers the quality of the gas itself once the compartment is filled or re-filled.

The practical consequence is that a field test programme has four mandatory gates:
Dielectric withstand - AC voltage proof on the main circuit, with the test level set by the field rule rather than the factory type-test value.
SF6 gas tightness - a measured leak rate per compartment, not a pressure gauge glance.
Gas quality - moisture and purity verified against the limits for in-service gas.
Partial discharge - a quantified PD measurement, normally UHF, recorded as a fingerprint.
Type tests, routine tests and field tests are three different things. A manufacturer's type-test report proves the design; it does not release the installation. Only the on-site evidence releases the bay for energization.