Test Object
meet test voltage 25kV,and capacitor not more than 2.5uF AC Hipot test
main technical parameters and functions
Rated capacity:500kVA;
Rated voltage:25kV;
Rated current:20A;
Working frequency:50Hz;
Output voltage waveform distortion rate:≤0.5%;
Allow continuous working hours: At rated load 5min;
Continuous operation under rated load 5min temperature rise≤65K;
quality factor: Q≥10;
System measurement accuracy: 1.5 effective value;
Input power: single phase 380V,50Hz;
It has over-current, over-voltage, and flashover protection for the test product;
environment temperature:-100C –50 0C,relative humidity:≤90%RH,altitude≤1000m;
Equipment complies with standards
GB10229-88 《reactor》
GB1094 《power transformer》
GB50150-2016 《the standard for electrical equipment handover and commission test》
DL/T 596-1996 《preventive testing rule of electrical equipment》
GB1094.1-GB1094.6-96 《Shell protection grade》
GB2900 《electrotechnical terminology》
GB/T16927.1~2-1997 《High voltage test technique》
Test power and L,Cx
|
Capacitor |
Adjustable reactor range |
|
0.5~2.5uF |
4.1H~20.3H |
Note: Cx test object capacity
|
Reactor capacity(kVA) |
Test voltage (kV) |
Test current (A) |
Range |
(H) |
|
|
Adjustable reactor |
500kVA |
25kV |
20A |
0.5-2.5 |
4.1-20.3H |
HYDK--500kVA/25kV
Rated capacity:500KVA;
Rated voltage:25kV;
Rated current:20A;
Adjustable inductance value:4.1-20.3H;
Quality factor: Q≥10;
Structure: dry type
Weight: about 600Kg