Product Introduction
Tested application and requirement
1. 220KV GIS AC voltage withstand test, test frequency is 30~300Hz, test voltage is not more than 395KV, test time is 1min.
2. 110KV GIS AC voltage withstand test, test frequency is 30~300Hz, test voltage is not more than 265KV, test time is 1min.
3. 35KV GIS AC voltage withstand test, test frequency is 30~300Hz, test voltage is not more than 95KV, test time is 1min.
Work condition
environment temperature:-100C –50 0C;
2. relative humidity:≤90%RH
3. altitude: ≤1000m
Main technical parameters and functions
rated capacity:800kVA;
input power: 3 phase 380V, 50Hz;
rated voltage:80kV;160KV, 400KV
rated current: 10A;4A;2A;
working frequency:30-300Hz;
output waveform: sine wave
waveform deviation factor Distortion rate of output voltage waveform≤1%;
working time: underrated load allowed continuous working 60min, over-voltage 1.1 times 1min;
Temperature rise: underrated load allowed continuous working 60min, after that temperature rise≤65K
quality factor: Q≥30(f=45Hz)
defensive function: Over-current, over-voltage, and flashover protection are provided for the tested product (see frequency conversion power supply for details).
accuracy: System effective value 1.5;
AC resonant test system operation video
Product Parameter
800kVA/400kV is design 10 reactors, and 80kVA/40kV/2A/60H for single reactor.
|
Combination Test object |
Reactor 80kVA/40kV*10 |
Excitation transformer output selection |
Test voltage (kV) |
|
220KV GIS |
connect 10 reactors in series |
24kV |
≤395kV |
|
110 KV GIS |
connect 7 reactors in series |
24KV |
≤265kV |
|
35KV GIS |
connect 3 reactors in series |
6KV |
≤95kV |
System and parameters
exciting transformer JLB-37kVA/6/12/24kV/0.4kV 1set
rated capacitance:55kVA;
input voltage:0-400V,single phase;
output voltage:6/12/24kV
Structure: dry type;
weight:180kg;variable frequency power supply CHXB-F -37kW/380V 1 set
Rated output capacity:37kW
Power supply for working: 380±10%V(single/3phase),power frequency
output voltage:0 –400V,single,
Rated input current:92.5A
rated output current:92.5A
Voltage resolution: 0.01kV
Accuracy of voltage measurement:1.5%
Frequency range:30 – 300Hz
Frequency control resolution:≤0.1Hz
frequency stability: 0.1%
Running time:Continuous at rated capacity 5min
Continuous at rated capacity 5minmax temperature of components≤65K
The noise level:≤50dB
The following functions can be implemented
Variable frequency power supply is placed vertically and horizontally, especially suitable for field operation and observation.
Inside and outside are equipped with special shock-absorbing rubber support feet and a protective aluminum box, which can effectively reduce bump vibration during transportation and shock during lifting. Guaranteed long-term stability and reliability of variable frequency power supply;
parameter display: Touch or external mouse large screen LCD system. Display resonant voltage (the target voltage set before the test), Test frequency, measurement frequency, low-voltage voltage, low-voltage current, withstand voltage time, overvoltage protection, overcurrent protection, flashover protection, step boosting and timing, operation mode switching, Capacitance, inductance, frequency interchange calculation, parameter query, can also display frequency curve, voltage curve and so on to directly judge the resonance frequency accuracy and stability of the test.
parameter setting: Large screen touch LCD color screen and external mouse directly complete the setting of various parameters, can set start frequency, stop frequency, start voltage, phase boost and timing, measurement of voltage divider variation ratio, excitation variation ratio, overvoltage protection, overcurrent protection, flashover protection, test mode, capacitance, and inductance frequency interchange calculation, parameter setting tips and help, etc.
Weight: About 35kg
HV reactor DK-80kVA/40kV 10nos
Rated capacitance:80kVA;
Rated voltage:40kV;
Rated current:2A;
inductance:60H /nos
quality factor:Q≥30 (f=45Hz);
Structure:dry type;
weight: about 65kg;
capacitive voltage divider FRC-400kV/500pF 1 set
Rated voltage:400kV;
HV capacitance:500pF;
dielectric loss:tgσ≤0.5%;
ratio of voltage divider:6000:1
measurement accuracy: active value 1.5
weight:about 35kg;
Product Feature And Application
Packing list
configuration equipment list
|
no |
name |
Model and specification |
unit |
Qty |
remarlk |
|
1 |
Exciting transformer |
JLB-37kVA/6/12/24kV/0.4kV |
set |
1 |
|
|
2 |
variable-frequency power supply |
CHXB-F-37kW/380V |
set |
1 |
|
|
3 |
High voltage reactor |
DK-80kVA/40kV |
set |
1 |
|
|
4 |
capacitive voltage divider |
FRC-400kV/500pF |
set |
1 |
|
|
6 |
Internal connection wires |
set |
1 |
Documents list
|
No |
name |
unit |
qty |
remark |
|
1 |
Ex-Factory test report |
copy |
1 |
|
|
2 |
manual |
copy |
1 |
|
|
3 |
Product certificates and customer comment CARDS |
set |
1 |
Prodection Details




FAQ
1. Delivery: Fast delivery and Flexible mode of transportation
2. Payment: Choose payment terms and payment way you convenient
3. Sale service: 24-hour online contact, Choose the right model of equipment according to your request, give the best offer, support customization
4. Warranty period: All machine quality guarantees for one year and lifetime technical support for you. Online response to customers' technical problems.
Production Line

Onsite test cases






Customer visit

Our certificates

Hot Tags: 800kva 400kv ac resonance test system for 220 kv gis, China 800kva 400kv ac resonance test system for 220 kv gis manufacturers, suppliers, factory, DC earth resistance tester, capacitive voltage transformer testing, 50A transformer winding resistance tester, Variable Frequency Resonant Test System, partial discharge detector with gps, 3 Phase Microcomputer Protection Relay Tester