Product Introduction
Measuring dielectric Loss is a basic method in insulation tests, which can effectively find the deterioration damp of insulators on electrical equipment as well as local defects. It is widely used in electrical manufacturing, electrical equipment installation, handover, and preventive tests. It is the most basic way to evaluate the insulation of electric equipment by measuring the dielectric losses of its transformers, instrument transformers, reactors, capacitors, bushing, and arresters.
Product Parameter
|
Work condition |
-15℃∽40℃ |
RH<80% |
|
|
Principle of anti-interference |
Variable frequency |
||
|
Power supply |
AC 220V±10% |
Permissible generator |
|
|
Output high voltage |
0.5KV∽10KV(can make 12kV) |
Every each 0.1kV |
|
|
Accuracy |
2% |
||
|
Max current |
200mA |
||
|
Capacitance |
2000VA |
||
|
self-excitation power supply |
AC 0V∽50V/15A |
50HZ,60HZ single frequency,45HZ/55HZ,47.5HZ/52.5HZ,55HZ/65HZ,57.5HZ/62.5HZ,Automatic double frequency conversion |
|
|
resolution |
tgδ: 0.001% |
Cx: 0.001pF |
|
|
Accuracy |
△tgδ:±(reading*1.0%+0.040%) |
||
|
△C x :±(reading*1.0%+1.00PF) |
|||
|
Test range |
tgδ |
No limitation |
|
|
C x |
15pF < Cx < 300nF |
||
|
10KV |
Cx < 60 nF |
||
|
5KV |
Cx < 150 nF |
||
|
1KV |
Cx < 300 nF |
||
|
CVT test |
Cx < 300 nF |
||
|
LCR test range |
L>20H(2kV) |
R>10KΩ(2kV) |
|
|
LCR test accuracy |
1% |
angular resolution |
0.01 |
|
CVT turn ratio range |
10∽10000 |
||
|
CVT turn ratio accuracy |
1% |
CVT turn ratio resolution |
0.01 |
|
size(host)(mm) |
350(L)×270(W)×270(H) |
||
|
size(accessory)(mm) |
350(L)×270(W)×160(H) |
||
|
Memory capacity |
200 group Support U disk data storage |
||
|
weight(host) |
22.75Kg |
||
|
weight(accessory) |
5.25Kg |
||
Model
|
|
JS-H |
JS-V |
JS-R |
|
UST mode |
√ |
√ |
√ |
|
GST mode |
√ |
√ |
√ |
|
CVT self-excitation mode |
√ |
√ |
√ |
|
C1/C2 test simultaneously |
|
√ |
√ |
|
External standard voltage |
|
√ |
√ |
|
External high voltage |
|
√ |
√ |
|
CVT turn ratio |
|
√ |
√ |
|
CVT test |
√ |
√ |
√ |
|
UST/GST test simultaneously |
|
√ |
√ |
|
LCR auto test |
|
√ |
√ |
|
Insulation resistance test |
|
|
√ |
|
USB connection |
|
√ |
√ |
|
U disk storage |
√ |
√ |
√ |
Product Feature And Application
1. Big touched screen LCD display: easy to use and no need to train the user, only click the screen to finish the whole test process
2. High storage capacity: can save 200 group data, results can be saved in chronological order, historical records can be viewed at any time, and can be printed out;
3. data management: The instrument data can be exported through a U disk, and can be viewed and managed on any PC.
4. Multiple test modes: It can test by internal high voltage, external high voltage, internal standard, external standard, positive connection method, reverse connection method, self-excitation method, and other methods; High voltage (> 10kV) dielectric loss can be made under the condition of external standard external high voltage.
5. CVT test:can test CVT(capacitor voltage transformer)C1/C2 of dielectric loss and capacitance,can test C1/C2 simultaneously. Can also test CVT Variation ratio and voltage Angle difference;
6. no need to remove the high voltage cable to test CVT: can test CVT dielectric loss and capacitance with no need to remove HV cable
7. CVT Reverse connection shielding measuring C0: can test the dielectric loss value and capacitance value of CVT upper C0
8. high-speed sampling signal: The inverter and sampling circuit inside the instrument are all controlled digitally, and the output voltage is continuously adjustable.
9. LCR full auto test: Automatic display inductance, capacitance, resistance measurement, Angle.
10. multiple protection features: such as input voltage fluctuation, high voltage current, output short circuit, power supply fault, overvoltage, overcurrent and temperature, etc., to ensure the safety and reliability of the instrument. also equipped with a grounding detection function to ensure that the ungrounded equipment does not allow voltage boost.
Prodection Details



Accessory
|
Serial Number |
Name |
Amount |
|
1 |
Inter-frequency dielectric loss tester |
one |
|
2 |
High voltage cable |
one |
|
3 |
Low voltage cable |
two |
|
4 |
Power line |
one |
|
5 |
Ground lead |
one |
|
6 |
CVT Line |
one |
|
7 |
5A Fuse (Internal) |
two |
|
8 |
Printing paper (50ml) |
one |
|
9 |
Specification |
one |
|
10 |
Inspection Report |
one |
|
11 |
Certification |
one |
FAQ
1. Delivery: Fast delivery and Flexible mode of transportation
2. Payment: Choose payment terms and payment way you convenient
3. Sale service: 24-hour online contact, Choose the right model of equipment according to your request, give the best offer, support customization
4. Warranty period: All machine quality guarantees for one year and lifetime technical support for you. Online response to customers' technical problems.
Customer Visit

On Site Service

Packing detail

Our service
01
Pre-sale service
Conduct product consultation, product promotion, and marketing activities, and technical support for customer needs.
02
Delivery service
Packing with wooden cases, provide different solutions of shipping way, accept different payment way. Save shipping cost and make sure the products arrive well.
03
After-sales service
Installation and commissioning of specific products; Respond to consumer questions, answer consumer inquiries, and deal with consumer comments.

Hot Tags: transformer dissipation factor test set, China transformer dissipation factor test set manufacturers, suppliers, factory, Transformer Tan Delta Tester, Tan Delta Tester, dga testing, Transformer Dissipation Factor Test Set, hipot wire vlf testing