Knowledge

What is the Duval Triangle, and how does it classify transformer faults?

May 15, 2026 Leave a message

Q: I hear about the "Duval Triangle" a lot in DGA interpretation. How does it work?

A: The Duval Triangle (by Michel Duval, IREQ, now IEEE C57.104) is the most widely used graphical method for DGA fault classification using a ternary diagram.

The three gas ratios (Triangle 1 - mineral oil):

• %CH₄ = CH₄ / (CH₄ + C₂H₄ + C₂H₂) × 100

• %C₂H₄ = C₂H₄ / (CH₄ + C₂H₄ + C₂H₂) × 100

• %C₂H₂ = C₂H₂ / (CH₄ + C₂H₄ + C₂H₂) × 100

Zone

Fault Type

Description

PD

Partial Discharge

Low-energy corona, sparking in voids

D1

Low-energy Discharge

Sparking, tracking (glow discharge)

D2

High-energy Discharge

Arcing with power follow-through

T1

Thermal < 300°C

Overheated insulation (winding or core)

T2

Thermal 300°–700°C

Hot spot, bad electrical connection

T3

Thermal > 700°C

Severe hot spot, possible arcing + thermal

DT

Mixed Thermal + Discharge

Combination fault

Example diagnosis:

A 150 MVA transformer: CH₄ = 180 ppm, C₂H₄ = 280 ppm, C₂H₂ = 5 ppm

%CH₄ = 38.7%, %C₂H₄ = 60.2%, %C₂H₂ = 1.1%

→ Falls in T2 zone → thermal fault 300–700°C.

High C₂H₄ + low C₂H₂ → likely a bad bolted connection or tap-changer contact.

Action: Inspect tap-changer contacts. Schedule outage if C₂H₄ continues rising.

Other Duval Triangles:

Triangle

Application

Key Difference

Triangle 1

Mineral oil transformers (standard)

CH₄, C₂H₄, C₂H₂

Triangle 2

Thermal fault zone refinement

CH₄, C₂H₄, C₂H₆

Triangle 3

Low-temperature thermal faults

C₂H₄, C₂H₆, CH₄

Triangle 4

Load Tap Changers (LTCs)

Same gases, different zone boundaries

Triangle 5

Natural ester (vegetable oil)

Adjusted boundaries for ester oils

Limitations:

• Requires at least three hydrocarbon gases above detection limits.

• Less reliable when one gas > 80% of total HC.

• Cannot distinguish multiple simultaneous fault types.

• Always use with gas generation rates (ppm/day or ppm/month).

Send Inquiry