How to distinguish flashover from breakdown during an AC Hipot test?

May 18, 2026 Leave a message

During the test, I saw a large spark and the relay tripped. Was it a flashover or a breakdown - and how do I tell the difference?

 

Distinguishing flashover (external surface discharge) from breakdown (internal puncture) is critical because the corrective action is completely different.

 

Definitions (IEC 60060-1):

• Flashover: Discharge across the SURFACE of an insulator (external - insulation may be intact).

• Breakdown / Puncture: Discharge THROUGH solid or liquid insulation (internal - permanent damage).

 

Observation

Flashover (External)

Breakdown (Internal)

Visible discharge path

Along the bushing surface or air gap

Through insulation - may not be visible

Sound

Loud, sharp "crack" (air ionization)

Duller "thump" (through oil/paper)

Arc location

Visible between the live terminal and the ground

Internal; no surface path visible

Post-test IR

Normal (insulation intact)

Drops significantly (compromised)

Post-test Tanδ

Normal or slightly elevated

Dramatically increased

Post-test DGA

No change

C₂H₂, H₂ if puncture arcs through oil

 

Decision tree:

1. Was the discharge path visible on the surface?

→ YES = flashover → clean, dry, re-test.

→ NO = could be internal. Measure IR → if low = breakdown.

2. Was discharge repetitive at the same voltage?

→ YES = internal defect (will repeat).

→ NO = random surface flashover (contamination).

 

Key practical rule:

• Flashover is a test setup failure, not equipment failure.

• Internal breakdown IS equipment failure - repair or replace.

• Always document: voltage at discharge, weather conditions, surface contamination.