Knowledge

Explore the knowledge about patial discharge test of power transformer

Aug 21, 2026 Leave a message

Q1: Why is frequency doubling (150Hz to 200Hz) mandatory for induced-voltage PD tests on a 40 MVA transformer?

A: When testing a transformer's longitudinal insulation (inter-turn and inter-layer), we apply a voltage significantly higher than the rated value (typically 1.5x). If we used a standard 50Hz/60Hz source, the iron core would immediately enter magnetic saturation, causing the excitation current to spike and potentially destroy the windings. According to the magnetic flux formula (Φ=U/4.44fNΦ=U/4.44fN), by increasing the frequency to 150Hz or 200Hz, we can achieve the high test voltage while keeping the core flux at a safe, non-saturated level.

 

Q2: How can we achieve a background noise level of < 10pC during an onsite 66kV transformer test?

A: Achieving such low noise in a field environment requires a systematic approach:

Hardware Filtering: Using a Variable Frequency Power Source with an integrated heavy-duty LC filter to block high-frequency noise from the IGBT switching.

Electric Field Optimization: Installing a large-diameter Grading Shield (Corona Ring) on the 66kV bushings to eliminate air corona.

Grounding Logic: Implementing a single-point star grounding system to prevent ground loops that act as antennas for EMI.

Cabling: Using double-shielded measurement cables to protect sensitive PD signals from ambient interference.

 

Q3: What are the pass/fail criteria for a 66kV transformer PD test according to IEC 60076-3?

A: For transformers with Um=72.5 kVUm​=72.5 kV (66kV class), the standard generally requires that during the long-term induced voltage monitor (typically at 1.5Um/31.5Um​/3​), the Partial Discharge level must remain below 100pC. Crucially, the PD trend must be stable; any continuous increase in discharge magnitude or pulse rate during the 30–60 minute test duration is considered a failure, even if the absolute value is below 100pC.

 

Q4: Can I use a standard AC Hipot Test Transformer instead of a Variable Frequency System?

A: A traditional test transformer can perform the Separate Source Withstand Test (main insulation to ground). However, it is not suitable for the more critical Induced Voltage Test on a 40MVA unit because it cannot provide the required increased frequency (150Hz+) to avoid core saturation. Furthermore, traditional test transformers are extremely heavy and difficult to transport to remote 66kV substations compared to modular Variable Frequency systems.

 

Q5: What is the advantage of using a 2D/3D PRPD fingerprint library in the diagnostic software?

A: The Phase-Resolved Partial Discharge (PRPD) library allows engineers to move beyond simple "Pass/Fail" results. By comparing the discharge patterns (shape, phase position, and frequency) against a database of known defects, the system can automatically identify the type of flaw-such as a sharp protrusion on a conductor, a floating metallic particle in the oil, or a void in the solid insulation. This "Expert System" significantly reduces the risk of human error during onsite data analysis.

Send Inquiry