500KV Variable Frequency Series Resonance Test System

Jan 03, 2024 Leave a message

Variable Frequency Series Resonance Test System adopts the method that adjusts the frequency of the power supply, making the reactor and tested capacitor get resonance and the HV high current available from tested equipment. This is a new method and trend at present, widely applied at home and abroad. The tester equipment is composed of a variable frequency power supply, excitation transformer, reactor, and capacitor. The capacitor and reactor of tested equipment constitute the form of a series resonant connection. A Voltage divider is in parallel in testing equipment, which is used to test the resonant voltage it and as the over-voltage protective signal. The frequency power output through the excitation transformer is coupled to a series resonant circuit, providing excitation power of series resonance.

 

500kva 500kv AC hipot tester application as below;

22kV---meet the ac hipot test for 10kV/300mm2 cable 5km,capacitance≤1.8775uF,test
frequency 30-300Hz,test voltage not over 22kV,test time 5min.
52kV---meet the ac hipot test for 35kV/300mm2cable 1.2km,capacitance≤0.2334uF,test
frequency 30-300Hz,test voltage not over 52kV,test time60min
128kV---meet the ac hipot test for 110kV/630mm2 cable 0.2km,meet the ac hipot test
for≤0.0376uF,test frequency 30-300Hz,test voltage not over 128kV,test time60min.
265kV---meet the ac hipot test 110kVGIS,switchgear,CT PT,test frequency 30-300Hz,
test voltage not over265kV,test time1min.
495kV---meet the ac hipot test for 110kVGIS,switchgear,CT PT,test frequency 30-300Hz,
test voltage not over265kV,test time 1min.
80kV---meet the ac hipot test 110kV/63000kVA main transformer neutral point,capacitance
≤0.02uF,test frequency 45-65Hz,test voltage 80kV,test time1min.
160kV---meet the ac hipot test for 220kV/63000kVA main transformer neutral point,
capacitance≤0.02uF,capacitance45-65Hz,test voltage160kV,test voltage 1min.
400kV---meet the ac hipot test for 220kV busbar,length70m,test frequency 30-300Hz,test
voltage not over 400kV,test time 1min.