Q: Why do we care about a few hundred milliohms (mΩ) in the CT winding?

A: Because internal resistance is part of the Total Burden. It limits how much voltage the CT can produce before it saturates.

The Logic:

• CT must produce voltage: Es = Is × (Rct + Rburden).

• High Rct (loose contact/damage) → CT works harder → Saturates early.

• Result: Protection Relay fails to see fault current correctly.

 

How to measure the  Secondary Winding Resistance of CT. 

Our HYCT-100  CT Analyzer is a new product created after widely adopting customers' advice and deep theoretical study. It is based on the automatic FA Series Transformer Tester General, which is produced by our company and is widely acclaimed and applied. The adoption of high-performance DSP and

ARM, advanced manufacturing technology ensure a stable and reliable product performance. full-featured, high degree of automation, high efficiency, in the domestic leading level, they are the professional testing equipment for transformer check in the power industry.
Secondary Winding Resistance test range 0~300Ω; accuracy: 0.2%±2mΩ